CyberPower OL1-10KVA UPS User Manual

Browse online or download User Manual for Uninterruptible power supplies (UPSs) CyberPower OL1-10KVA UPS. CyberPower OL1-10KVA UPS User manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - PARAGON SERIES

PARAGON SERIES USER MANUAL OL1-10KVA UPS Uninterruptible Power Supply

Page 2 - Contents

-7- 4. System Description Figure 1: Display Panel Switch Function ON - Switch Turn on UPS system: By pressing the ON-Switch “I” the UP

Page 3

-8- 13: BATTERY LED The green-coloured BATTERY-LED lights up when the utility power has failed and the inverter is being powered by the batteries. 1

Page 4 - 1.1 Installation

-9- 5. Connection and Operation for OL1000TEXL/ OL1000EXL-M/OL2000TEXL/OL2000EXL-M/OL3000TEXL/OL3000EXL-M 5.1 Inspection: Inspect the packa

Page 5 - 1.2 Operation

-10- Besides output sockets, the OL2000EXL-M and OL3000TEXL/ OL3000EXL-M units have a terminal block available for output as well. The terminal bloc

Page 6 - 1.5 Storage

-11- 5.3 Charge Battery: Fully charge the batteries of the UPS system by leaving the UPS system connected to the utility power for 1-2 hours. You ma

Page 7 - 1.6 Standards

-12- 5.6.2 In Battery Mode: Press “ “ button for more than 1 second to turn off the UPS. Then the UPS enter into self-test status. After finishing t

Page 8

-13- 6. Trouble Shooting If the UPS system does not operate correctly, please attempt to solve the problem using the table below. Problem Possible c

Page 9 - OL2000TEXL/OL2000EXL-M/

-14- 7. Maintenance 7.1 Operation The UPS system contains no user-serviceable parts. If the battery service life (3 - 5 years at 25°C ambient temper

Page 10 - 4. System Description

-15- 8. Technical Data 8.1 Electrical specifications Model No. OL1000TEXL/ OL1000EXL-M OL2000TEXL/ OL2000EXL-M OL3000TEXL/ OL3000EXL-M INPUT Phase

Page 11

-16- 8.4 Dimensions and weights Model No. Dimensions W x D x H (mm) Net Weight (kg) OL1000TEXL 145X400X220 14 OL1000EXL-M 145X400X220 7 OL2000TE

Page 12 - OL3000TEXL/OL3000EXL-M

Contents 1. Safety and EMC Instructions...1 1.1 Installation...

Page 13

-17- 9. Product Specification and Performance– OL6000TEXL/OL6000EXL-M/ OL10000TEXL/OL10000EXL-M 9.1 General Specification Model OL6000TEXL OL6000EXL

Page 14 - 5.6 Power off the UPS:

-18- 9.3 Operating Environment Temperature Humidity Altitude Storage temperature 0°C-40°C <95% <1000m 0°C-40° Note: if the UPS is installe

Page 15

-19- 10. Installation 10.1 Unpacking and Inspection 10.1.1 Unpack the packaging and check the package contents. The shipping package contains: l A UP

Page 16 - 6. Trouble Shooting

-20- UPS, please refer to the appearance diagram. 10.2.2.2 For OL6000TEXL/OL6000EXL-M UPS, it is recommended to select the UL1015 10AWG(6mm2) wire or

Page 17 - 7. Maintenance

-21- less than optimum. 10.2.2.11 If it is necessary to connect an inductive load such as a monitor or a laser printer to the UPS, the start-up power

Page 18 - 8. Technical Data

-22- 10.3.2.1 A DC breaker must be connected between the battery pack and the UPS. The capacity of breaker must be not less than the data specified i

Page 19 - 8.4 Dimensions and weights

-23- 10.4 Parallel operation 10.4.1 Brief introduction of the redundancy N+X is currently the most reliable power supply structure. N represents the

Page 20 - OL10000TEXL/OL10000EXL-M

-24- 11. Operation and maintenance 11.1 To perform the general operation, follow the stand-alone operating requirement. 11.2 Startup: The units tra

Page 21 - 9.3 Operating Environment

-25- is abnormal, the UPS will operate in battery mode without output interruption of the UPS. 11.3.2 Turn on the UPS with no utility power supplied

Page 22 - 10. Installation

-26- the UPS and turn on the loads one by one after the UPS is working in INV mode. Turn off all of the connected loads before turning off the UPS.

Page 23

10.3 Operating Procedure for Connecting the Extended Backup Time Model UPS with the External Battery...

Page 24

-27- 11.3.5.1.8 Close line input switch of all UPS(include new UPS) in the parallel system; lock up maintain board, unless all UPS turn to bypass mod

Page 25

-28- 11.3.5.3 Combine machine warning: 11.3.5.3.1 When UPS combine system work at inverter mode, make sure that all UPS maintain switches at the same

Page 26 - 10.4 Parallel operation

-29- 12. Battery Maintenance l This series UPS only requires minimal maintenance. The battery used for standard models are value regulated sealed lea

Page 27

-30- 13. Notes for Battery Disposal and Battery Replacement 1) Before disposing of batteries, remove conductive jewelry such as necklace, wrist watch

Page 28

-31- 14. Trouble Shooting Problem Possible cause Solution The #1 Fault LED and the #6 LED are turned on, the buzzer beeps continuously. The UPS tra

Page 29

-32- The #1 Fault LED is turned on, and the battery LED is flashed, the buzzer beeps every second. The charger of the UPS is defective. Please contac

Page 30

-33- 15. Operating mode for all models 1. Utility power mode The display panel in utility power mode is shown in the following diagram. The ac input

Page 31

-34- battery capacity. Note that the load level LEDs in utility power mode will indicate the level of the battery capacity in battery mode instead. 1

Page 32 - 12. Battery Maintenance

-35- 1) Other indications on the display panel are the same in utility mode. 2) The UPS does not have the backup function when it is in bypass mode.

Page 33 - Replacement

-36- 16. Communication Port 16.1 RS232 Interface The following is the pin assignment and description of DB-9 connector. 16.2 Serial to USB Adapter

Page 34 - 14. Trouble Shooting

-1- 1. Safety and EMC instructions 1.1 Installation ★ Condensation may occur if the UPS is moved directly from a cold to a warm environment. The UPS

Page 35

-37- 17. Software for all models Software CD — PowerPanel® Business Edition PowerPanel® Business Edition is a brand new UPS monitoring software, whi

Page 36 - 2. Battery mode

-38- Appendix 1-Display Panel (for OL6000TEXL /OL6000EXL-M/OL10000TEXL/ OL10000EXL-M) l Power ON/OFF: To turn on the UPS simply by press

Page 37 - 3. Bypass mode

-39- Appendix 2-The Corresponding Form of the LED Display for OL6000TEXL / OL6000EXL -M /OL10000TEXL/ OL10000EXL-M LED display No. Operating state 1

Page 38 - 4. Abnormality mode

-40- 13 overloaded in utility mode and UPS in bypass mode ● ● ● ● ● ● ● ● Beep twice every sec. 14 Utility power abnormal ● ↑ ↑ ↑ ↑

Page 39 - 16.3 AS400 Interface(Option)

-41- Appendix 3-Back Panel Back View of OL1000TEXL/OL1000EXL-M Back View of OL2000TEXL

Page 40 - 17. Software for all models

-42- Back View of OL2000 EXL-M/OL3000TEXL/OL3000EXL-M Back View of OL6000TEXL/OL6000EXL-M

Page 41 - OL10000EXL-M)

-43- Back View of Back View of OL10000TEXL/OL10000EXL-M

Page 43 - ★ : Flash

-45- 614-03710-00

Page 44 - Appendix 3-Back Panel

-2- ★ An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided

Page 45

-3- the UPS are still connected to the battery which are potentially dangerous. ★ Before carrying out any kind of service and/or maintenance, discon

Page 46

-4- 1.6 Standards For OL1000TEXL/OL1000EXL-M/OL2000TEXL/OL2000EXL-M/ OL3000TEXL/OL3000EXL-M * Safety IEC/EN 62040-1-1 * EMI Conducted Emission...

Page 47

-5- 2. Description of commonly used notations Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourse

Page 48 - 614-03710-00

-6- 3. Introduction – OL1000TEXL/OL1000EXL-M/ OL2000TEXL/OL2000EXL-M/OL3000TEXL/OL3000EXL-M The On-Line-Series is an uninterruptible power supply in