PowerPanel™ Business Edition
44
The dots and the line indicate the specific time and day of the week to notify the recipient of the event
Action Settings
Settings page allows for configuration of various event actions, including the necessary shutdown time of
the hosted computer.
After configuring all of the action parameters, and applying the settings, the Verify button can be used to
verify whether the user’s configurations are correct. To test whether a notification is configured properly and
a recipient can receive the notification successfully, use the Test function on the Event Action/Notification
Recipient page.
Each action has its own Activate option to specify whether to use the service to send a notification. If No is
checked, the Verify button and the corresponding Test function will be disabled. The column displayed in
the recipient list will be marked gray to indicate that action is disabled.
Shutdown
z Necessary shutdown time: This setting will set the amount of time which Agent and Client will take to
shut down. The host computer will initiate the shutdown before power is stopped from the PDU or UPS in
order to avoid a sudden blackout. This setting should be configured to allow for the normal shutdown
time of the computer.
When Client connects to a PDU outlet, the shutdown time must be set properly to avoid the delay-off
time of the connected inability to support a complete shutdown. When a PDU performs a sequenced
off/reboot action, each outlet has a specified delay time (delay-off) before it is turned off. This delay time
must be greater than the Necessary shutdown time required by a Client computer. The Client will
communicate with the PDU to verify whether this delay time is sufficient. If the delay time is insufficient a
warning message will display. The user can expand it and configure the outlet delay-off of the PDU or
configure it in the PDU web interface manually. The warning message will be visible until these options
are setup properly.
Note: This function must have write permission. See Security/Authentication
for more details. If the
Client is given write permission on the PDU it can setup the PDU directly.