4 Maintenance
4.1 Troubleshooting
If any
of LEDs
22
23
or
24
flash, there is
an alarm or
an
abnormal
operation.
See the table below for
problems and solution.
If an LED flashes,
the bargraph data is no longer displayed.
Indication
LED
24
flashes and the buzzer sounds.
Signification
UPS overload. Overload is too long or too high.
- If AC power is present and within tolerance, the UPS changes to
bypass mode (supplied directly by
the AC outlet). LED
16
flashes. The buzzer sounds every
second.
- If AC power is not present or not within tolerances, the connected
equipment is no longer supplied
with power. The buzzer sounds
continuously.
Correction
Check the power drawn by the
equipment and disconnect any short
current or non-priority devices.
Indication
ED
22
flashes and the buzzer sounds.
Signification
A battery fault was detected during the automatic battery test.
- Replace battery modules (see
4.2 Replacement of the battery
module
on page
23).
Correction
Check that the battery connector is fully pushed in.
Indication
LED
22
flashes and the buzzer emits a long
beep once per
hour.
Signification
The battery
has reached the end of its service life.
Replace battery modules (see
4.2 Replacement of the battery
module
on page
23).
Correction
- Reset the alarm by pressing buttons
19
and
20
simultaneously
for three seconds.
- It is advisable to replace the
entire
battery module with a
new
battery module that has the same rating as the
battery module that
is being replaced.
Maintenance 21