Note :
1.
Please do not turn the ATS PDU off and ensure the quality of selected
source power when
processing firmware upgrade. The ATS PDU will not
perform the ATS function when upgrading firmware.
2. Press “3” to exit the main menu of firmware upgrade.
RMCARD
There are two files to update in order to upgrade the firmware:
- cpssnmpfw_XXX.bin
- cpssnmpdata_XXX.bin
Note that the XXX is not part of the file name but is where the version number
in the filename is given.
Use the following steps to upgrade the firmware.
1.
Download the latest firmware from cpsww.com
2.
Extract the file to “C:\”
3.
Open a command prompt window and navigate to “C:\”
4.
Login to the Remote Management Card with FTP command, type
-
ftp (after entering ftp mode, ftp> will display in the command prompt as
shown below instead of C:\ )
-
ftp> open
-
To [current IP of the RMCARD] [port] (for example: To 192.168.22.126 21
[21 is the default ftp port for the RMCARD])
-
Input USER NAME and PASSWORD (same as the administrator account in
Web interface default: cyber ; cyber)
5.
Upload the cpssnmpfw_XXX.bin, type
-
ftp > bin
-
ftp > put cpssnmpfw _XXX.bin
6
.
Upgrade complete, type
-
ftp > quit7.
The system will reboot after you type “quit”. This reboot will
take approx. 30 seconds
8.
Login to the FTP again
-
ftp
-
ftp> open
-
To [current IP of the RMCARD] [port] (for example: To 192.168.22.126 21)
[21 is the default ftp port for theRMCARD])
-
Input USER NAME and PASSWORD
9.
Upload cpssnmpdata _XXX.bin
-
ftp > bin
-
ftp > put cpssnmpdata _XXX.bin
10.
Upgrade complete , type
-
ftp > quit
11. The system will reboot after you type “quit”
Troubleshooting
Problem Possible Cause Solution
ATS PDU outlets do
not provide power to
connected equipment
1. Breaker tripped
2. Power cord is not
properly plugged in
Reset Breaker, check the plug to
insure its connected correctly. If
the problem remains, contact
technical support.
Amperage displayed
on LCD Display
exceeds the units
capability
Overload
The load indicator shows red
when overload. Reduce the load
on the ATS PDU until the overload
is gone. If the problem remains,
contact technical support.
Circuit breakers have
tripped
1. Sustained overload
2. Excessive ambient or
internal temperatures
3. Faulty breaker
Reset Breaker.
If the problem remains, contact
technical support.