o Turn off when utility power fails for minutes: Sets how long the
utility power is off before turning off this outlet. The valid value is 0-
120.
o Turn on when utility power restores for minutes: Sets how long
the utility power has restored before turning on this outlet. The valid
value is 0-120.
*Enter bypass mode once the Battery Backup is overloaded: If you
enable this option, the Battery Backup will supply utility power directly to
the load when there is an overload condition. Otherwise, the Battery Backup
will shutdown. An overload occurs when the load is over 110%.
*Enter bypass mode when the Battery Backup turns off: If you enable
this option, the Battery Backup supply utility power directly to the load
when the Battery Backup turns off. Otherwise, the Battery Backup will
shutdown.
*Allow bypass even when utility power is out of range: If you enable
this option, even if utility power is out of range, the Battery Backup still
enters bypass mode.
*Wake up the Battery Backup when utility power is restored: If you
enable this option, the Battery Backup will wake up when utility power is
restored.
*The Battery Backup can start without utility power and supply
battery power: If you enable this option, the Battery Backup can start
without utility power. After startup, the Battery Backup will supply battery
power to the connected equipment.
*The Battery Backup will attempt to restore power from a short
circuit condition: If you enable this option, the Battery Backup will stop
supplying power to the connected equipment when a short circuit occurs.
The Battery Backup will attempt to restore power three times for 30 seconds
and continues supplying power if the short circuit condition disappears, the
Battery Backup will shutdown if short circuit condition remains. If you
disable this option, the Battery Backup will stop supplying power and
shutdown.
*Force rebooting of the Battery Backup when utility power is
restored early: If you enable this option, the Battery Backup will be forced
to reboot when utility power is restored early in the following manner. When
utility power fails, the connected computer may be asked to shutdown first
and the Battery Backup may shutdown too after a specific delay time. If the
utility power is restored earlier than this, the Battery Backup will stop
supplying output power for 10 seconds once the delay time is up. This
option is useful for you to ensure the connected computer will restart after a
power failure shutdown.
*Restore power when the batteries have been charged for amount
of minutes: Sets time for recharging when the Battery Backup restores
power. The batteries must be recharging for the amount of time to restore
power. 0 minutes means the Battery Backup will restore power immediately.
Note: This setting is available only if Wake up the Battery Backup when
utility power is restored is enabled.