CyberPower PDU20SW8RNET User Manual Page 74

  • Download
  • Add to my manuals
  • Print
  • Page
    / 133
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 73
72
PowerPanel
Secret Phrase. The Secret Phrase is used to create secure network communications between PowerPanel
®
Applications such as Client and Agent, Client and UPS RMCARD, or Client and PDU. The default phrase is
powerpanel.encryption.key. The Secret Phrase can be configured on the Security/Authentication page in the
Agent and Client, or on the System/Security page in the PDU and UPS RMCARD web. The Secret Phrase which is
used in the Client and devices must match.
Secret Phrase on the System/Security page in the UPS RMCARD202 web
Note: If the firmware version on the RMCARD202 is earlier than 1.1 (excluding 1.1), you should refer to SNMP,
SNMPv1 and SNMPv3 sections for the correct configurations.
SNMP
The Client establishes communication and access device information via SNMPv1 and SNMPv3. Early UPS and PDU
models only support SNMPv1 protocol, and some newer models have supported SNMPv3 protocol. User can choose
the proper SNMP protocol according to the device.
SNMP Protocol. User can determines which SNMP protocol to use over the network communication between Client
and devices. It is recommended to choose Both option because Client attempts on the correct SNMP protocol for
device to interact.
SNMPv1
SNMP Community. The Client uses this community to authenticate communication between the PDU and UPS in
order to access their information. The default community is private. By default, the UPS/PDU/ATS use private as the
Page view 73